High Reliability China Medium Voltage Frequency Inverter from Trusted Suppliers and Factory - 20 Years Fault-Free Operation
Model Meaning
- The dimensions and weight are for reference only; the exact dimensions and weight shall be as specified in the technical agreement.
- For standard series units, the input voltage is identical to the output voltage.
- The overall height does not include the height of the cooling fan; an additional 300 mm to 600 mm should be added for the fan height.
- The above overall dimensions and weight refer to the combined total of the control cabinet, power unit cabinet, and transformer cabinet excluding the line-frequency bypass cabinet.
- The minimum clearance requirements are as follows: at least 1500 mm from the front of the equipment to the wall, at least 1000 mm from the rear, at least 800 mm from either side, and at least 1000 mm from the top of the equipment to the ceiling.
- Standard overload capacity is 120% for 1 minute, allowed once every 10 minutes. Optional overload capacities of 125%, 150%, or 200% are available to meet different application requirements.
- The applicable motor power rating may vary depending on the motor type and construction, and is provided for reference only.
Model Selection
| Model | Motor Power (Kw) | Frequency Converter Capacity (Kva) | Weight (Kg) | Cabinet Type | Cabinet Dimensions (L×W×H) |
|---|---|---|---|---|---|
| SHMV100-06-185kW | 185 | 230 | 2650 | Cabinet A1 | 1900X1500X2000 |
| SHMV100-06-220kW | 220 | 275 | |||
| SHMV100-06-250kW | 250 | 320 | |||
| SHMV100-06-280kW | 280 | 350 | 2760 | ||
| SHMV100-06-315kW | 315 | 400 | |||
| SHMV100-06-355kW | 355 | 450 | 2930 | ||
| SHMV100-06-400kW | 400 | 500 | |||
| SHMV100-06-450kW | 450 | 560 | 3160 | ||
| SHMV100-06-500kW | 500 | 630 | 3360 | ||
| SHMV100-06-560kW | 560 | 700 | 3985 | Cabinet B1 | 2700X1500X2000 |
| SHMV100-06-630kW | 630 | 800 | 4042 | ||
| SHMV100-06-710kW | 710 | 900 | 4160 | ||
| SHMV100-06-800kW | 800 | 1000 | 4382 | ||
| SHMV100-06-900kW | 900 | 1150 | 4590 | ||
| SHMV100-06-1000kW | 1000 | 1250 | 4792 | ||
| SHMV100-06-1120kW | 1120 | 1400 | 4985 | ||
| SHMV100-06-1250kW | 1250 | 1600 | 5285 | ||
| SHMV100-06-1400kW | 1400 | 1800 | 6120 | Cabinet C1 | 3033X1650X2200 |
| SHMV100-06-1600kW | 1600 | 2000 | 6390 | ||
| SHMV100-06-1800kW | 1800 | 2250 | 6745 | ||
| SHMV100-06-2000kW | 2000 | 2500 | 7090 | ||
| SHMV100-06-2250kW | 2250 | 2800 | 9220 | Cabinet D1 | 5400X1400X2400 |
| SHMV100-06-2500kW | 2500 | 3200 | 9570 | ||
| SHMV100-06-2800kW | 2800 | 3500 | 10070 | ||
| SHMV100-06-3200kW | 3200 | 4000 | 10670 | ||
| SHMV100-06-3600kW | 3550 | 4500 | 11240 | ||
| SHMV100-06-4000kW | 4000 | 5000 | 12500 | Cabinet F1 | 6850X1400X2400 |
| SHMV100-06-4500kW | 4500 | 5650 | 13000 | ||
| SHMV100-06-5000kW | 5000 | 6300 | 14000 | ||
| SHMV100-06-5600kW | 5600 | 7000 | 17755 | Cabinet G1 | 8200X1600X2400/2600 |
| SHMV100-06-6300kW | 6300 | 8000 | 18795 | ||
| SHMV100-06-6600kW | 7100 | 9000 | 19450 | ||
| SHMV100-10-185kW | 185 | 230 | 2220 | Cabinet A | 2700X1500X2000 |
| SHMV100-10-220kW | 220 | 275 | 2240 | ||
| SHMV100-10-250kW | 250 | 320 | 2260 | ||
| SHMV100-10-280kW | 280 | 350 | 2286 | ||
| SHMV100-10-315kW | 315 | 400 | 2316 | ||
| SHMV100-10-355kW | 355 | 450 | 2346 | ||
| SHMV100-10-400kW | 400 | 500 | 2383 | ||
| SHMV100-10-450kW | 450 | 560 | 2433 | ||
| SHMV100-10-500kW | 500 | 630 | 2483 | ||
| SHMV100-10-560kW | 560 | 700 | 2593 | ||
| SHMV100-10-630kW | 630 | 800 | 2719 | ||
| SHMV100-10-710kW | 710 | 900 | 2875 | ||
| SHMV100-10-800kW | 800 | 1000 | 3062 | ||
| SHMV100-10-900kW | 900 | 1150 | 3192 | Cabinet B | 3033X1650X2200 |
| SHMV100-10-1000kW | 1000 | 1250 | 3258 | ||
| SHMV100-10-1120kW | 1120 | 1400 | 3409 | ||
| SHMV100-10-1250kW | 1250 | 1600 | 4390 | ||
| SHMV100-10-1400kW | 1400 | 1800 | 4648 | ||
| SHMV100-10-1600kW | 1600 | 2000 | 4948 | ||
| SHMV100-10-1800kW | 1800 | 2250 | 5270 | ||
| SHMV100-10-2000kW | 2000 | 2500 | 5604 | Cabinet C | 4000X1500X2200 |
| SHMV100-10-2250kW | 2250 | 2800 | 5916 | ||
| SHMV100-10-2500kW | 2500 | 3150 | 7990 | ||
| SHMV100-10-2800kW | 2800 | 3500 | 8150 | ||
| SHMV100-10-3200kW | 3200 | 4000 | 8700 | ||
| SHMV100-10-3600kW | 3550 | 4500 | 8820 | Cabinet D | 6925X1500X2455 |
| SHMV100-10-4000kW | 4000 | 5000 | 11990 | ||
| SHMV100-10-4500kW | 4500 | 5600 | 12500 | ||
| SHMV100-10-5000kW | 5000 | 6300 | 13300 | ||
| SHMV100-10-5500kW | 5600 | 7000 | 13800 | ||
| SHMV100-10-6300kW | 6300 | 8000 | 18410 | Cabinet E | 9100X1650X2455 |
| SHMV100-10-7100kW | 7100 | 9000 | 19700 | ||
| SHMV100-10-8000kW | 8000 | 10000 | 20400 | Cabinet F | 9200X1700X2800 |
| SHMV100-10-9000kW | 9000 | 11250 | 22500 | ||
| SHMV100-10-10000kW | 10000 | 12500 | 27120 | Cabinet G | 12200X1600X2455 |
| SHMV100-10-11000kW | 11000 | 13750 | 28860 |
Primary Circuit Diagram
Harmonic-Free Solution
The secondary winding of the phase-shifting transformer employs an extended delta connection, altering the phase angle of each secondary winding per phase.
- This mitigates the impact of harmonics generated by the unit on the power grid.
- Taking two units connected in series as an example for analysis: the phase-shift angle θ = 60°/2 = 30°
- The current is referred to the primary input side and expanded into a Fourier series:
The 5th, 7th, and 11th harmonic components have phase angles differing by 180°, and through phase-shifting rectification technology, these harmonics cancel each other out.
Take the input phase-shifting transformer of a 10kv variable frequency drive (VFD) as an example. Its primary winding is rated at 10kv, while the secondary side consists of 24 three-phase windings, each with an output voltage of 690v. Every winding adopts an extended delta connection and has a phase shift angle difference of 7.5°. This configuration can effectively eliminate harmonics below the 47th order, which means that 48-pulse rectification is capable of suppressing harmonics lower than the 47th order (calculated by the formula 6n-1, where n refers to the number of units per phase).
Industry Applications
Power Generation
Induced draft fans, primary/secondary air fans, circulating water pumps, boiler feed pumps, condensate pumps, slurry circulation pumps, vertical coal mills.
Oil, Gas & Chemicals
Electric submersible pumps (ESPs), injection pumps, crude oil transfer pumps, pipeline compressors, LNG compressors, air separation compressors, syngas compressors, ammonia refrigeration compressors "ice machines", product gas compressors, propylene compressors, carbon dioxide compressors.
Mining
Conveyor belts, main mine ventilation fans, methane drainage pumps, slurry pumps, crushers, semi-autogenous grinding (SAG) mills, ball mills, high-pressure roller mills.
Cement
Raw mill circulating fans, coal mill exhaust fans, cement mill exhaust fans, kiln inlet exhaust fans, kiln outlet high-temperature fans, kiln tail exhaust fans, clinker cooler fans, coal mills, roller presses.
Metallurgy
Dust collection fans, sintering main induced draft fans, blast furnace blowers, circulating water pumps, descaling pumps, slag granulation pumps, air separation compressors, grinding mills, stamping presses, bidirectional energy recovery compressors.
Municipal/Water Treatment
Raw water intake pumps, water supply pumps, primary lift pumps, secondary clear water pumps, seawater desalination pumps, booster pumps, irrigation pumps.
Waste-to-Energy
Various standard fans and pumps.
Main Features
Low-voltage ride-through (LVRT)
Auto-restart after power loss (within 20 seconds)
Power cell bypass function
Flying-start (spin-start) capability
Synchronous switching function
Redundant control power supply (optional)
Redundant power unit design (N+1, optional)
Redundant cooling fans (optional)
Other functions customizable per customer requirements
Dedicated control function module for mills
Magnetizing inrush current suppression cabinet
One-drive-one manual bypass cabinet
One-drive-two manual bypass cabinet
One-drive-one automatic bypass cabinet
One-drive-two automatic bypass cabinet
One-drive-one synchronous switching cabinet
Output reactor cabinet
Isolation cabinet
Frequently Asked Questions
Does the overall height specification of the equipment include the cooling fan?
No, the overall height does not include the height of the cooling fan. An additional 300 mm to 600 mm should be added to the cabinet height to account for the fan.
What are the minimum clearance requirements for installing the cabinet?
The minimum clearance requirements are: at least 1500 mm from the front of the equipment to the wall, at least 1000 mm from the rear, at least 800 mm from either side, and at least 1000 mm from the top of the equipment to the ceiling.
What is the standard overload capacity for these models?
The standard overload capacity is 120% for 1 minute, allowed once every 10 minutes. Optional overload capacities of 125%, 150%, or 200% are available to meet specific application requirements.
How does the system achieve a harmonic-free solution?
By employing an extended delta connection on the secondary winding of the phase-shifting transformer, the system alters the phase angle of each secondary winding. Using phase-shifting rectification technology (such as 48-pulse rectification with a 7.5° phase shift angle difference), harmonic components cancel each other out, effectively eliminating harmonics below the 47th order.
What happens to the VFD system during a brief power loss?
The system features an auto-restart after power loss capability, allowing it to safely restart within 20 seconds. It also includes low-voltage ride-through (LVRT) and flying-start (spin-start) capabilities to maintain stable operation.