High Reliability Medium Voltage Frequency Inverter from China Suppliers & Factory – 20-Year Fault-Free Operation
Hot Products

High Reliability Medium Voltage Frequency Inverter from China Suppliers & Factory – 20-Year Fault-Free Operation

,

Our product guarantees high reliability with the incorporation of 1700V high-voltage IGBTs (Insulated Gate Bipolar Transistors) sourced from reputable suppliers in China. This advanced technology ensures an exceptional average fault-free operation period of up to 20 years, making it an ideal choice for customers seeking quality and durability from a trusted factory.

,

    Model Meaning

    Model Meaning Diagram
    1. The dimensions and weight are for reference only; the exact dimensions and weight shall be as specified in the technical agreement.
    2. For standard series units, the input voltage is identical to the output voltage.
    3. The overall height does not include the height of the cooling fan; an additional 300 mm to 600 mm should be added for the fan height.
    4. The above overall dimensions and weight refer to the combined total of the control cabinet, power unit cabinet, and transformer cabinet excluding the line-frequency bypass cabinet.
    5. The minimum clearance requirements are as follows: at least 1500 mm from the front of the equipment to the wall, at least 1000 mm from the rear, at least 800 mm from either side, and at least 1000 mm from the top of the equipment to the ceiling.
    6. Standard overload capacity is 120% for 1 minute, allowed once every 10 minutes. Optional overload capacities of 125%, 150%, or 200% are available to meet different application requirements.
    7. The applicable motor power rating may vary depending on the motor type and construction, and is provided for reference only.

    Model Selection

    Model Motor Power(Kw) Frequency Converter Capacity(Kva) Weight(Kg) Cabinet Type Cabinet Dimensions(L×W×H)
    SHMV100-06-185kW 185 230 2650 Cabinet A1 1900X1500X2000
    SHMV100-06-220kW 220 275
    SHMV100-06-250kW 250 320
    SHMV100-06-280kW 280 350 2760
    SHMV100-06-315kW 315 400
    SHMV100-06-355kW 355 450 2930
    SHMV100-06-400kW 400 500
    SHMV100-06-450kW 450 560 3160
    SHMV100-06-500kW 500 630 3360
    SHMV100-06-560kW 560 700 3985 Cabinet B1 2700X1500X2000
    SHMV100-06-630kW 630 800 4042
    SHMV100-06-710kW 710 900 4160
    SHMV100-06-800kW 800 1000 4382
    SHMV100-06-900kW 900 1150 4590
    SHMV100-06-1000kW 1000 1250 4792
    SHMV100-06-1120kW 1120 1400 4985
    SHMV100-06-1250kW 1250 1600 5285
    SHMV100-10-185kW 185 230 2220 Cabinet A 2700X1500X2000
    SHMV100-10-220kW 220 275 2240
    SHMV100-10-500kW 500 630 2483
    SHMV100-10-1000kW 1000 1250 3258 Cabinet B 3033X1650X2200
    SHMV100-10-1800kW 1800 2250 5270

    Primary Circuit Diagram

    Primary Circuit Diagram

    Harmonic-Free Solution

    The secondary winding of the phase-shifting transformer employs an extended delta connection, altering the phase angle of each secondary winding per phase.

    • This mitigates the impact of harmonics generated by the unit on the power grid.
    • Taking two units connected in series as an example for analysis: the phase-shift angle o = 60°/2 = 30°
    • The current is referred to the primary input side and expanded into a Fourier series:
    Fourier Series
    Harmonic Cancellation

    The 5th, 7th, and 11th harmonic components have phase angles differing by 180°, and through phase-shifting rectification technology, these harmonics cancel each other out.

    Take the input phase-shifting transformer of a 10kv variable frequency drive (VFD) as an example. its primary winding is rated at 10kv, while the secondary side consists of 24 three-phase windings, each with an output voltage of 690v. Every winding adopts an extended delta connection and has a phase shift angle difference of 7.5°. This configuration can effectively eliminate harmonics below the 47th order, which means that 48-pulse rectification is capable of suppressing harmonics lower than the 47th order.

    Phase Shifting Config

    Industry Applications

    Power Generation Induced draft fans, primary/secondary air fans, circulating water pumps, boiler feed pumps, condensate pumps, slurry circulation pumps, vertical coal mills.
    Oil, Gas & Chemicals Electric submersible pumps (ESPs), injection pumps, crude oil transfer pumps, pipeline compressors, LNG compressors, air separation compressors, syngas compressors.
    Mining Conveyor belts, main mine ventilation fans, methane drainage pumps, slurry pumps, crushers, semi-autogenous grinding (SAG) mills, ball mills.
    Cement Raw mill circulating fans, coal mill exhaust fans, cement mill exhaust fans, kiln inlet exhaust fans, kiln outlet high-temperature fans.
    Metallurgy Dust collection fans, sintering main induced draft fans, blast furnace blowers, circulating water pumps, descaling pumps, slag granulation pumps.
    Municipal/Water Treatment Raw water intake pumps, water supply pumps, primary lift pumps, secondary clear water pumps, seawater desalination pumps.

    Main Features

    • Low-voltage ride-through (LVRT)
    • Auto-restart after power loss (within 20 seconds)
    • Power cell bypass function
    • Flying-start (spin-start) capability
    • Synchronous switching function
    • Redundant control power supply (optional)
    • Redundant power unit design (N+1, optional)
    • Redundant cooling fans (optional)
    • Dedicated control function module for mills
    • Magnetizing inrush current suppression cabinet
    • One-drive-one/two manual and automatic bypass cabinets
    • Output reactor cabinet & Isolation cabinet

    Frequently Asked Questions

    What is the standard overload capacity of the system?
    The standard overload capacity is 120% for 1 minute, allowed once every 10 minutes. Optional capacities of 125%, 150%, or 200% are available.
    How does the VFD handle a sudden power loss?
    The system features an auto-restart function that can resume operation after a power loss within 20 seconds.
    Does the system require specific clearance for installation?
    Yes, minimum clearance is 1500mm from the front, 1000mm from the rear, 800mm from either side, and 1000mm from the top to the ceiling.
    How are harmonics managed in this 10kV VFD?
    It uses a 48-pulse rectification configuration through a phase-shifting transformer, effectively eliminating harmonics below the 47th order.
    Are redundant components available for higher reliability?
    Yes, we offer optional redundant control power supplies, redundant power unit designs (N+1), and redundant cooling fans.
    Is the input voltage different from the output voltage?
    For standard series units, the input voltage is identical to the output voltage.