High Voltage Solid State Soft Starter - SHMV-YTG Series | China Suppliers & Factory Solutions for Medium Voltage Motors
Structural Features
Applications
Widely used in power systems, metallurgy, mining, petroleum, chemical, water treatment and other industries for high voltage squirrel-cage AC asynchronous & high-voltage synchronous motors.
Voltage Range: 3.3~10KV | Power Range: 220KW~5600KW.
Performance and Parameters
- Control mode: kick start, voltage ramp, constant current, speed control (Optional).
- Starting mode: soft start, straight up, soft stop, free stop.
- Operation mode: Cabinet, external control, communication remote control (optional).
- Communication: RS 485 interface: Modbus/Profibus protocol (optional).
- Analog output: motor operating current, signal 0-10V or 4-20mA.
- Initial voltage: 10% to 50% (expandable to 5%-80% Un).
- Current limiting: 100% to 400% In (expandable to 500%In).
- Start/stop time: 1~30S (expandable to 90S).
- LCD display: current, starts, running time, failure, multi-language support.
- Noise: <80db.
- Cooling: Natural cooling.
- Protection class: IP42 (IP54 optional).
Working Environment and Conditions
• Temperature: Running: -10°C to 50°C | Storing: -20°C to 70°C.
• Humidity: ≤ 95% at +50°C.
• Environment: Free of explosion hazards and corrosive gases. Pollution level: ≤ 3.
• Altitude: < 1000m (expandable to 4000m).
• Vibration: 10Hz to 150Hz, acceleration not more than 0.5m/s².
• Power Supply: 10KV/50Hz fluctuation -15%~+10%.
System Diagram and Appearance
Product Selection & Size
| Model | Voltage (kV) | Current (A) | Power (kW) | Dimensions WxDxH (mm) |
|---|---|---|---|---|
| SHMV-YTG-3.3-50 | 3.3 | 50 | 220 | 1000X1500X2300 (Std) 800X1500X2300 (Cust) |
| SHMV-YTG-3.3-100 | 3.3 | 100 | 450 | |
| SHMV-YTG-3.3-150 | 3.3 | 150 | 630 | |
| SHMV-YTG-3.3-200 | 3.3 | 200 | 900 | 1000X1500X2300 |
| SHMV-YTG-3.3-400 | 3.3 | 400 | 1800 | 1200X1500X2300 |
| SHMV-YTG-6-50 | 6 | 50 | 400 | 1000X1500X2300 (Std) 800X1500X2300 (Cust) |
| SHMV-YTG-6-100 | 6 | 100 | 800 | |
| SHMV-YTG-6-150 | 6 | 150 | 1250 | |
| SHMV-YTG-10-50 | 10 | 50 | 690 | 1000X1500X2300 (Std) 800X1500X2300 (Cust) |
| SHMV-YTG-10-200 | 10 | 200 | 2800 | |
| SHRMV-YTG-10-400 | 10 | 400 | 5600 | 1200X1500X2300 |
Note: Typical product data. Parameters based on actual product.
Technical Indicators
General Information
| Main Power Supply | 2300V - 11000V (+10% -15%) |
| Frequency | 45~65Hz (Automatic adjustment) |
| Control Voltage | 110~230V (+10% -15%) |
| Insulation Level | Up to 32,500V for 11000V systems |
Motor Protection
| Start Times Limit | 1 to 10 starts in 1 to 60 minute cycle |
| Stall Protection | Trips if full beam not reached within 1-30s (ext 90s) |
| Electronic Overload | 75%~150% FLA adjustable curves |
| Phase Protection | Phase loss, sequence, and imbalance protection |
| Voltage Protection | Under voltage (50%-125%) and Over voltage (110%-125%) |
| Thermal Protection | Heatsink overtemperature trip at 85°C |